YLAA0070 - YLAA0175AIR-COOLED SCROLL CHILLERSMICROCHANNEL CONDENSER COILSSTYLE A (60 Hz)70 - 175 TON246-613 KWINSTALLATION, OPERATION, MAINTENANCEAIR-
JOHNSON CONTROLS10FORM 150.72-NM1 (908)LIST OF FIGURESFIG. 1 – UNIT COMPONENTS FRONT ...
JOHNSON CONTROLS100FORM 150.72-NM1 (908)Technical DataSLRS SEISMIC ISOLATOR INSTALLATION AND ADJUSTMENTTO INSTALL AND ADJUST MOUNTS1. Supports for
FORM 150.72-NM1 (908)101JOHNSON CONTROLS55FOR UNITS WITH ALL POINT LOADS LESS THAN 1404 LBS (637 KG)Weight Range (lbs) Weight Range (kg) Model Number
JOHNSON CONTROLS102FORM 150.72-NM1 (908)Technical Data1. Floor or steel frame should be level and smooth.2. For pad installations, isolators do
FORM 150.72-NM1 (908)103JOHNSON CONTROLS55Weight Range (lbs)Weight Range (kg)Model Number Color YORK P/NUp to 751 lbs Up to 341 kg ND-C Yellow 029-245
JOHNSON CONTROLS104FORM 150.72-NM1 (908)Technical DataENGLISHSIZE H T D E L HCL W HCW MBD2-C2 8-1/2” 3/8” 5/8” 1-3/8” 14” 12-1/4” 5-1/4” 3-1/
FORM 150.72-NM1 (908)105JOHNSON CONTROLS55SLRS SEISMIC ISOLATOR INSTALLATION AND ADJUSTMENTTO INSTALL AND ADJUST MOUNTS1. Supports for mountings must
JOHNSON CONTROLS106FORM 150.72-NM1 (908)CommissioningCOMMISSIONING -
FORM 150.72-NM1 (908)107JOHNSON CONTROLS6Supply VoltageVerify that the site voltage supply corresponds to the unit requirement and is within the lim
JOHNSON CONTROLS108FORM 150.72-NM1 (908)CommissioningJOB NAME: ______________________________SALES ORDER #: _________________________LOCATION: ______
FORM 150.72-NM1 (908)109JOHNSON CONTROLS6 4. Put the unit into Service Mode (as described under the Control Service and Troubleshooting section) and
FORM 150.72-NM1 (908)11JOHNSON CONTROLSLIST OF TABLESTABLE 1 – TEMPERATURES AND FLOWS ...
JOHNSON CONTROLS110FORM 150.72-NM1 (908)CommissioningCHECKING SUPERHEAT AND SUBCOOLINGThe subcooling temperature of each system can be calculat
FORM 150.72-NM1 (908)111JOHNSON CONTROLS6The operating sequence described below relates to operation on a hot water start after power ha
JOHNSON CONTROLS112FORM 150.72-NM1 (908)Unit ControlsSECTION 7 – UNIT CONTROLSYORK MILLENNIUM CONTROL CENTERThe YORK MicroComputer Control Center
FORM 150.72-NM1 (908)113JOHNSON CONTROLS7The on-board power supply converts 24 VAC from 75 VA, 120/24 VAC 50/60Hz UL listed class 2 power trans
JOHNSON CONTROLS114FORM 150.72-NM1 (908)Unit Controls“STATUS” KEYUnit StatusPressing the STATUS key will enable the operator to determine current chil
FORM 150.72-NM1 (908)115JOHNSON CONTROLS7This message informs the operator that the chilled liquid temperature is below the point (determined b
JOHNSON CONTROLS116FORM 150.72-NM1 (908)Unit ControlsThe Suction Pressure Cutout is a software cutout that helps protect the chiller from an evaporato
FORM 150.72-NM1 (908)117JOHNSON CONTROLS7During the 30 minute timeout, the MP/HPCO INHIB message will be displayed. The MP/HPCO fault will only be
JOHNSON CONTROLS118FORM 150.72-NM1 (908)Unit ControlsUnit SafetiesUnit safeties are faults that cause all running compressors to be shut down. Unit fa
FORM 150.72-NM1 (908)119JOHNSON CONTROLS7STATUS KEY MESSAGESTABLE 8 – STATUS KEY MESSAGES QUICK REFERENCE LISTLD11297BSTATUS KEY MESSAGESGeneral Messa
JOHNSON CONTROLS12FORM 150.72-NM1 (908)General Chiller Introduction & SafetySECTION 1 – GENERAL CHILLER INFORMATION & SAFETYINTRODUCTIONYORK Y
JOHNSON CONTROLS120FORM 150.72-NM1 (908)Unit ControlsThe Display/Print keys allow the user to retrieve system and unit information that is useful
FORM 150.72-NM1 (908)121JOHNSON CONTROLS7S Y S X S P = 7 2 . 1 P S I G D P = 2 2 7 . 0 P S I GThes
JOHNSON CONTROLS122FORM 150.72-NM1 (908)Unit Controls *Refer to the section on O P E R AT I N G CONTROLS.If the micro is programmed for CUR
FORM 150.72-NM1 (908)123JOHNSON CONTROLS7See the section on Condenser Fan Control in the UNIT OPERATION section for more information.The fth messag
JOHNSON CONTROLS124FORM 150.72-NM1 (908)Unit ControlsPrint KeyThe PRINT key allows the operator to obtain a printout of real-time system operating dat
FORM 150.72-NM1 (908)125JOHNSON CONTROLS7History DisplaysThe HISTORY key
JOHNSON CONTROLS126FORM 150.72-NM1 (908)Unit ControlsDisplays the programmed Low Ambient Cutout.Di sp lays the Leaving Liqu id Temp. C ut out p
FORM 150.72-NM1 (908)127JOHNSON CONTROLS7Displays which system is in the lead at the time of the fault.Displays status of the Evaporator Heater at the
JOHNSON CONTROLS128FORM 150.72-NM1 (908)Unit ControlsThe Entry Keys allows the user to view, change programmed values. The ENTRY keys consist of an ↑
FORM 150.72-NM1 (908)129JOHNSON CONTROLS7Programming of the cooling setpoints, daily schedule, and safeties is accomplished by using the keys located
FORM 150.72-NM1 (908)13JOHNSON CONTROLS1• Manufactured in facility registered to ISO 9002.• OSHA – Occupational Safety and Health Act.In addit
JOHNSON CONTROLS130FORM 150.72-NM1 (908)Unit Controls(leaving chilled liquid control)(return chilled liquid control)The low limit, high limit, and def
FORM 150.72-NM1 (908)131JOHNSON CONTROLS7* Refer to Engineering Guide for operation below 30 °F (-1.1 °C). Alternate thermal expansion valves must b
JOHNSON CONTROLS132FORM 150.72-NM1 (908)Unit ControlsPROGRAM KEYThere are several operating parameters under the PROGRAM key that are programmab
FORM 150.72-NM1 (908)133JOHNSON CONTROLS7The Number of Fans Per System must
JOHNSON CONTROLS134FORM 150.72-NM1 (908)Unit ControlsUnit Trip VoltsFor total chiller high current trip programming on 460VAC chillers: • Add
FORM 150.72-NM1 (908)135JOHNSON CONTROLS7TABLE 12 – SETPOINTS QUICK REFERENCE LISTLD07404cTable 16 provides a quick reference of the setpoints list fo
JOHNSON CONTROLS136FORM 150.72-NM1 (908)Unit ControlsThis allows both systems to runorThis turns system 2 offThis turns system 1 offorThis turns syste
FORM 150.72-NM1 (908)137JOHNSON CONTROLS7Option 4 – Ambient Control Type:The low ambient cutout is adjustable from 25 °F to 60 °F (-3.9 °C to 15.6 °C
JOHNSON CONTROLS138FORM 150.72-NM1 (908)Unit ControlsOption 12 – Power Fail Restart:Chiller auto restarts after a power failure.After a power failu
FORM 150.72-NM1 (908)139JOHNSON CONTROLS7 Option 16 – Expansion Valve Type:Expansion valve t
JOHNSON CONTROLS14FORM 150.72-NM1 (908)General Chiller Introduction & SafetyGeneral AccessThere are a number of areas and features, which may be a
JOHNSON CONTROLS140FORM 150.72-NM1 (908)Unit Controls Y O R K H Y D R O K I T P U M P S =
FORM 150.72-NM1 (908)141JOHNSON CONTROLS7TABLE 13 – UNIT KEYS OPTIONS PROGRAMMING QUICK REFERENCE LISTTable 13 provides a quick reference list for the
JOHNSON CONTROLS142FORM 150.72-NM1 (908)Unit OperationCAPACITY CONTROLTo initiate the start sequence of the chiller, all run permissive input
FORM 150.72-NM1 (908)143JOHNSON CONTROLS8FIG. 22 – LEAVING WATER TEMPERATURE CONTROL EXAMPLEHot gas, if present, will be the nal step of capacity. Ho
JOHNSON CONTROLS144FORM 150.72-NM1 (908)Unit OperationRETURN CHILLED LIQUID CONTROL(Can be used on Dual System 4, 5 & 6 Comp Units Only)Ret
FORM 150.72-NM1 (908)145JOHNSON CONTROLS8RETURN CHILLLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCINGA lead/Lag option may be selected t
JOHNSON CONTROLS146FORM 150.72-NM1 (908)Unit OperationANTI-RECYCLE TIMERThe programmable anti-recycle timer assures that systems do not cycle.
FORM 150.72-NM1 (908)147JOHNSON CONTROLS8FIG. 24 – CONDENSER FAN LOCATIONSWIRING DIAGRAMSCONTROL PANELCONTROL PANELCONTROL PANELCONTROL PANELCONTROL P
JOHNSON CONTROLS148FORM 150.72-NM1 (908)Unit OperationTABLE 17 – YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (2, 3, OR 4 FANS P
FORM 150.72-NM1 (908)149JOHNSON CONTROLS8TABLE 18 – YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (5 OR 6 FANS PER SYSTEM)FAN STA
FORM 150.72-NM1 (908)15JOHNSON CONTROLS2SECTION 2 – PRODUCT DESCRIPTIONINTRODUCTIONYORK YLAA Air-Cooled Scroll Chillers provide chilled water for
JOHNSON CONTROLS150FORM 150.72-NM1 (908)Unit OperationRESERVED FOR FUTURE LOW AMBIENT KIT
FORM 150.72-NM1 (908)151JOHNSON CONTROLS8RESERVED FOR FUTURE LOW AMBIENT KIT
JOHNSON CONTROLS152FORM 150.72-NM1 (908)Unit OperationRESERVED FOR FUTURE LOW AMBIENT KIT
FORM 150.72-NM1 (908)153JOHNSON CONTROLS8RESERVED FOR FUTURE LOW AMBIENT KIT
JOHNSON CONTROLS154FORM 150.72-NM1 (908)Unit OperationRESERVED FOR FUTURE LOW AMBIENT KIT
FORM 150.72-NM1 (908)155JOHNSON CONTROLS8LOAD LIMITINGLoad Limiting is a feature that prevents the unit from loading beyond the desired value. 2 and 4
JOHNSON CONTROLS156FORM 150.72-NM1 (908)Unit OperationBAS/EMS TEMPERATURE RESET USING A VOLTAGE OR CURRENT SIGNALThe Remote Reset Option allows t
FORM 150.72-NM1 (908)157JOHNSON CONTROLS9SYS 1 COMP 3 STATUS TB7-5 IS:SYS 1 HGBP STATUS TB7-7 IS:SYS 2 COMP 1 STATUS TB10-2 IS:SYS 2 LLSV STATUS TB10-
JOHNSON CONTROLS158FORM 150.72-NM1 (908)Service and TroubleshootingPressing the ↑ (UP) arrow key will energize the liquid line solenoid valve and “OFF
FORM 150.72-NM1 (908)159JOHNSON CONTROLS9 F L O W S W / R E M S T A R T J 13 - 5 I S O NTABLE 23 – I/O ANALOG
JOHNSON CONTROLS16FORM 150.72-NM1 (908)Product DescriptionThe evaporator is constructed, tested and stamped in accordance with applicable secti
JOHNSON CONTROLS160FORM 150.72-NM1 (908)Service and TroubleshootingFIG. 25 – MICROBOARD LAYOUTTB5TB1TB6TB7TB8TB9TB10J14J13J12J15J11J10J9J8J7J6J5J3I/O
FORM 150.72-NM1 (908)161JOHNSON CONTROLS9CHECKING INPUTS AND OUTPUTSDigital InputsRefer to the unit wiring diagram. All digital inputs are connected t
JOHNSON CONTROLS162FORM 150.72-NM1 (908)Service and TroubleshootingLiquid & Refrigerant Sensor Test Points (Table 25)Entering Chilled Liquid Senso
FORM 150.72-NM1 (908)163JOHNSON CONTROLS9Analog Inputs – PressureRefer to the unit wiring diagram. Pressure inputs are connected to the microboard o
JOHNSON CONTROLS164FORM 150.72-NM1 (908)Service and TroubleshootingFIG. 26 – I/O BOARD RELAY CONTACT ARCHITECTURELD12722The suction transducers have
FORM 150.72-NM1 (908)165JOHNSON CONTROLS9LD12723The micro panel is capable of supplying a printout of chiller conditions or fault shutdown information
JOHNSON CONTROLS166FORM 150.72-NM1 (908)Service and TroubleshootingTROUBLESHOOTING PROBLEM CAUSE SOLUTIONNo display on panel. 1. No 115VAC to 24 V
FORM 150.72-NM1 (908)167JOHNSON CONTROLS9 PROBLEM CAUSE SOLUTION“LOW SUCTION PRESSURE” 4. TXV defective. 4. Replace TXV.FAULT (CONT’D) 5. Reduce
JOHNSON CONTROLS168FORM 150.72-NM1 (908)Service and Troubleshooting PROBLEM CAUSE SOLUTION“MP / HPCO” FAULT 1. Compressor internal motor 1. Verif
FORM 150.72-NM1 (908)169JOHNSON CONTROLS10SECTION 10 – MAINTENANCEIt is the responsibility of the equipment owner to provide maintenance on the system
FORM 150.72-NM1 (908)17JOHNSON CONTROLS2 UNIT ON/OFF switchThe microprocessor control center is capable of displaying the following: • Return a
JOHNSON CONTROLS170FORM 150.72-NM1 (908)MaintenanceReceived Data (Control Data)The unit receives 8 data values from the ISN. The rst 4 are analog
FORM 150.72-NM1 (908)171JOHNSON CONTROLS10TABLE 29 – ISN TRANSMITTED DATA (CONT’D)ISN CONTROL (CON’T)ISN PAGECHARACTER TYPE DATAP38 110 DigitalEvapora
JOHNSON CONTROLS172FORM 150.72-NM1 (908)Maintenance P56/58 OPERATIONAL CODE P57/59 FAULT CODE 0 NO ABNORMAL CONDITION 0 NO FAULT 1 UNIT SWITC
FORM 150.72-NM1 (908)173JOHNSON CONTROLS10Data can be read and in some cases modied using a serial communication BACnet or Modbus netw
JOHNSON CONTROLS174FORM 150.72-NM1 (908)MaintenanceThe table below shows the minimum, maximum, and default values.TABLE 31 – MINIMUM, MAXIMUM AND DEFA
FORM 150.72-NM1 (908)175JOHNSON CONTROLS10TABLE 32 - REAL TIME ERROR NUMBERSERROR NUMBER (##)DESCRIPTION0 ALL OK1 DATUM TYPE OK TEST FAILED2 ENGLISH T
JOHNSON CONTROLS176FORM 150.72-NM1 (908)MaintenanceChiller data that can be read and modied using specic Modbus Register Addresses; and the data ass
FORM 150.72-NM1 (908)177JOHNSON CONTROLS10AI BACNET NAME ANALOG INPUT DESCRIPTION12 S1_EEV_OUT SYS 1 EEV OUTPUT % (EEV ONLY)13 S1_AR_TIMER SYS 1 ANTI-
JOHNSON CONTROLS178FORM 150.72-NM1 (908)MaintenanceSERIAL COMMUNICATION BINARY INPUT DATAThis data can be read using a BACnet or Modbus network connec
FORM 150.72-NM1 (908)179JOHNSON CONTROLS10194YORK INTERNATIONALTemperature Conversion Chart -Actual TemperaturesTEMPERATURE CONVERSION CHARTTemperatur
JOHNSON CONTROLS18FORM 150.72-NM1 (908)Product DescriptionACCESSORIES AND OPTIONSPOWER OPTIONSCOMPRESSOR POWER CONNECTIONS – Single-point termina
PSIG TEMP ˚F PSIG TEMP ˚F0 -60 78 202 -58 80 214 -54 85 246 -50 90 268 -46 95 2910 -42 100 3212 -39 105 3414 -36 110 3616 -33 115 3918 -30 120 4120 -2
FORM 150.72-NM1 (908)19JOHNSON CONTROLS2DX COOLER 300 (21 BAR) PSIG DWP WATERSIDE – The waterside will be of 300 PSIG (21 bar) instead of the standard
JOHNSON CONTROLS2FORM 150.72-NM1 (908)This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, in
JOHNSON CONTROLS20FORM 150.72-NM1 (908)Product DescriptionSOUND ATTENUATION – One or both of the following sound attenuation options are recommended f
FORM 150.72-NM1 (908)21JOHNSON CONTROLS2FIG. 1 – UNIT COMPONENTS FRONTUNIT COMPONENTS COMPRESSORSEVAPORATORSIGHTGLASSCONDENSER COILSCONDENSER COILFILT
JOHNSON CONTROLS22FORM 150.72-NM1 (908)Product DescriptionFIG. 2 – UNIT COMPONENTS SIDEUNIT COMPONENTS (CONT)FAN ASSEMBLIESCONDENSER COILSCONDENSER CO
FORM 150.72-NM1 (908)23JOHNSON CONTROLS2LD13247FIG. 3 – POWER PANEL COMPONENTSCONTROL / POWER PANEL COMPONENTS COMPRESSOR CONTACTORSXTBF1FAN CONTACTOR
JOHNSON CONTROLS24FORM 150.72-NM1 (908)Product DescriptionCONTROL / POWER PANEL COMPONENTS (CONT) FIG. 4 – POWER PANEL / CONTROL COMPONENTSCOMPRESSOR
FORM 150.72-NM1 (908)25JOHNSON CONTROLS2PRODUCT IDENTIFICATION NUMBER (PIN)BASIC UNIT NOMENCLATUREYLAA0150EE 46XAA: Standard Efciency: High Efciency
JOHNSON CONTROLS26FORM 150.72-NM1 (908)Product DescriptionPRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)FEATURE DESCRIPTION OPTION DESCRIPTIONREF REFRIGE
FORM 150.72-NM1 (908)27JOHNSON CONTROLS2PRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)FEATURE DESCRIPTION OPTION DESCRIPTIONRDOUT READOUT KITS (PIN 23) B
JOHNSON CONTROLS28FORM 150.72-NM1 (908)Product DescriptionPRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)FEATURE DESCRIPTION OPTION DESCRIPTIONFLOW FLOW S
FORM 150.72-NM1 (908)29JOHNSON CONTROLS2PRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)FEATURE DESCRIPTION OPTION DESCRIPTIONPIN51 PIN 51 X XQ SPECIAL QUO
FORM 150.72-NM1 (908)3JOHNSON CONTROLSCHANGEABILITY OF THIS DOCUMENTIn complying with YORK’s policy for continuous product improvement, the informatio
JOHNSON CONTROLS30FORM 150.72-NM1 (908)Product DescriptionPRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)FEATURE DESCRIPTION OPTION DESCRIPTIONPKGOPTPUMP
FORM 150.72-NM1 (908)31JOHNSON CONTROLS2FIG. 6 – PROCESS AND INSTRUMENTATION DIAGRAMPROCESS AND INSTRUMENTATION DIAGRAMLow pressure liquid refrigerant
JOHNSON CONTROLS32FORM 150.72-NM1 (908)Handling and StorageSECTION 3 – HANDLING AND STORAGEDELIVERY AND STORAGETo ensure consistent quality and maximu
FORM 150.72-NM1 (908)33JOHNSON CONTROLS3FIG. 7 – UNIT RIGGING/LIFTING Use spreader bars to avoid lifting chains hitting the chiller.
JOHNSON CONTROLS34FORM 150.72-NM1 (908)Installation
FORM 150.72-NM1 (908)35JOHNSON CONTROLS4Ground Level LocationsIt is important that the units be installed on a substantial base that will not sett
JOHNSON CONTROLS36FORM 150.72-NM1 (908)InstallationDrain connections should be provided at all low points to permit complete drainage of the cooler an
FORM 150.72-NM1 (908)37JOHNSON CONTROLS4DUCT WORK CONNECTION General Requirements The following duct work recommendations are intended to ensure satis
JOHNSON CONTROLS38FORM 150.72-NM1 (908)InstallationAlarm Status ContactsNormally-open contacts are available for each re frigerant system. These norma
FORM 150.72-NM1 (908)39JOHNSON CONTROLS4FIG. 9 – SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCH OR CIRCUIT BREAKERSINGLE
JOHNSON CONTROLS4FORM 150.72-NM1 (908)TABLE OF CONTENTSSECTION 1 – GENERAL CHILLER INFORMATION & SAFETY ...
JOHNSON CONTROLS40FORM 150.72-NM1 (908)InstallationFIG. 10 – CONTROL WIRING INPUTSUSER CONTROL WIRING INPUTS
FORM 150.72-NM1 (908)41JOHNSON CONTROLS4FIG. 11 – CONTROL WIRING OUTPUTSUSER CONTROL WIRING OUTPUTS
JOHNSON CONTROLS42FORM 150.72-NM1 (908)Technical DataOPERATIONAL LIMITATIONS (ENGLISH)VOLTAGE LIMITATIONSThe following voltage limitations are absolut
FORM 150.72-NM1 (908)43JOHNSON CONTROLS55Note: Water Pressure Drop Curves may extend past the minimum and maximum water ow ranges. HEAT EXCHANGER FLO
JOHNSON CONTROLS44FORM 150.72-NM1 (908)Technical DataPHYSICAL DATA (ENGLISH)YLAA0070_ – YLAA0175_TABLE 4 – PHYSICAL DATA (ENGLISH)60HzRefrigerant R-41
FORM 150.72-NM1 (908)45JOHNSON CONTROLS55Refrigerant R-410AModel Number YLAA Model Number YLAASTANDARD EFFICIENCY UNITS HIGH EFFICIENCY UNITS0070SE 00
JOHNSON CONTROLS46FORM 150.72-NM1 (908)Technical Data-
FORM 150.72-NM1 (908)47JOHNSON CONTROLS55ELECTRICAL NOTESLEGEND ACR-LINE ACROSS THE LINE START C.B. CIRCUIT BREAKER D.E. DUAL ELEMENT FUSE DISC
JOHNSON CONTROLS48FORM 150.72-NM1 (908)Technical DataELECTRICAL DATA W/O PUMPSCHILLERMODELVOLT HZMINIMUM CIRCUIT AMPSMIN N/F DISC SWMIN DUAL ELEM FUSE
FORM 150.72-NM1 (908)49JOHNSON CONTROLS55CHILLERMODELVOLT HZMINIMUM CIRCUIT AMPSMIN N/F DISC SWMIN DUAL ELEM FUSE & MIN CBMAX DUAL ELEM FUSE &
FORM 150.72-NM1 (908)5JOHNSON CONTROLSTABLE OF CONTENTS (CONT’D)SECTION 4 – INSTALLATION ...
JOHNSON CONTROLS50FORM 150.72-NM1 (908)Technical DataELECTRICAL DATA W/O PUMPS (Continued)CHILLERMODELVOLT HZMINIMUM CIRCUIT AMPSMIN N/F DISC SWMIN DU
FORM 150.72-NM1 (908)51JOHNSON CONTROLS55CHILLERMODELVOLT HZMINIMUM CIRCUIT AMPSMIN N/F DISC SWMIN DUAL ELEM FUSE & MIN CBMAX DUAL ELEM FUSE &
JOHNSON CONTROLS52FORM 150.72-NM1 (908)Technical DataCHILLER MODEL VOLT HZTERMINAL BLOCK LUGSNON FUSED DISCONNECT SWITCH LUGS TERMINAL BLOCK LUGSYLAA0
FORM 150.72-NM1 (908)53JOHNSON CONTROLS55CHILLER MODEL VOLT HZTERMINAL BLOCK LUGSNON FUSED DISCONNECT SWITCH LUGS TERMINAL BLOCK LUGSP1: YLAA0115 &
JOHNSON CONTROLS54FORM 150.72-NM1 (908)Technical DataELECTRICAL DATA W/ PUMPSCHILLERMODELVOLTPUMPMODELPUMPFLAMINIMUMCIRCUITAMPSMIN N/F DISC SWMIN DUAL
FORM 150.72-NM1 (908)55JOHNSON CONTROLS55CHILLERMODELVOLTPUMPMODELPUMPFLAMINIMUMCIRCUITAMPSMIN N/F DISC SWMIN DUALELEM FUSE & MIN CBMAX DUALELEM F
JOHNSON CONTROLS56FORM 150.72-NM1 (908)Technical DataELECTRICAL DATA W/ PUMPS (continued)CHILLERMODELVOLTPUMPMODELPUMPFLAMINIMUMCIRCUITAMPSMIN N/F DIS
FORM 150.72-NM1 (908)57JOHNSON CONTROLS55CHILLERMODELVOLTPUMPMODELPUMPFLAMINIMUMCIRCUITAMPSMIN N/F DISC SWMIN DUALELEM FUSE & MIN CBMAX DUALELEM F
JOHNSON CONTROLS58FORM 150.72-NM1 (908)Technical DataELECTRICAL DATA W/ PUMPS (continued)CHILLERMODELVOLTPUMPMODELPUMPFLAMINIMUMCIRCUITAMPSMIN N/F DIS
FORM 150.72-NM1 (908)59JOHNSON CONTROLS55CHILLERMODELVOLTPUMPMODELPUMPFLAMINIMUMCIRCUITAMPSMIN N/F DISC SWMIN DUALELEM FUSE & MIN CBMAX DUALELEM F
JOHNSON CONTROLS6FORM 150.72-NM1 (908)ELECTRICAL NOTES AND LEGEND ...
JOHNSON CONTROLS60FORM 150.72-NM1 (908)Technical DataELECTRICAL DATA W/ PUMPS (continued)CHILLERMODELVOLTPUMPMODELPUMPFLAMINIMUMCIRCUITAMPSMIN N/F DIS
FORM 150.72-NM1 (908)61JOHNSON CONTROLS55CHILLERMODELVOLTPUMPMODELPUMPFLAMINIMUMCIRCUITAMPSMIN N/F DISC SWMIN DUALELEM FUSE & MIN CBMAX DUALELEM F
JOHNSON CONTROLS62FORM 150.72-NM1 (908)Technical DataELECTRICAL NOTES AND LEGENDNOITPIRCSEDnoitangiseDNOITPIRCSEDnoitangiseDREKAERB TIUCRICBCQ-YROSSEC
FORM 150.72-NM1 (908)63JOHNSON CONTROLS55ELECTRICAL NOTES AND LEGEND (CONTINUED)GENERALA. This drawing is based on IEC symbols.B. Field wiring to be i
JOHNSON CONTROLS64FORM 150.72-NM1 (908)Technical DataWIRING DIAGRAMSLD13143AFIG. 12 – ELEMENTARY WIRING DIAGRAM035-21583-101 REV BELEMENTARY WIRING DI
FORM 150.72-NM1 (908)65JOHNSON CONTROLS55LD13144A
JOHNSON CONTROLS66FORM 150.72-NM1 (908)Technical DataLD13145AFIG. 13 – ELEMENTARY WIRING DIAGRAM035-21583-102 REVC
FORM 150.72-NM1 (908)67JOHNSON CONTROLS55LD13146A
JOHNSON CONTROLS68FORM 150.72-NM1 (908)Technical DataCONDENSER FAN MAPPING AND SEQUENCINGLD13147FIG. 14 – CONDENSER FAN MAPPING AND SEQUENCING
FORM 150.72-NM1 (908)69JOHNSON CONTROLS55LD13232
FORM 150.72-NM1 (908)7JOHNSON CONTROLSPREPARATION – POWER ON ...
JOHNSON CONTROLS70FORM 150.72-NM1 (908)Technical DataCOMPRESSOR WIRINGLD13900FIG. 15 – COMPRESSOR WIRING035-21589-106 REVC
FORM 150.72-NM1 (908)71JOHNSON CONTROLS55LD13233A
JOHNSON CONTROLS72FORM 150.72-NM1 (908)Technical DataPOWER OPTIONS CONNECTION DIAGRAMFIG. 16 – POWER OPTIONS CONNECTION DIAGRAMLD13234A035-21589-103 R
FORM 150.72-NM1 (908)73JOHNSON CONTROLS55LD13901
JOHNSON CONTROLS74FORM 150.72-NM1 (908)Technical DataPOWER PANELLD13235AFIG. 17 – POWER PANEL035-21589-101 REV B
FORM 150.72-NM1 (908)75JOHNSON CONTROLS55LD13236A
JOHNSON CONTROLS76FORM 150.72-NM1 (908)Technical DataDUAL PUMP WIRINGLD13237FIG. 18 – DUAL PUMP WIRING
FORM 150.72-NM1 (908)77JOHNSON CONTROLS55This Page Intentionally Left Blank
JOHNSON CONTROLS78FORM 150.72-NM1 (908)Technical DataWIRINGLD13238FIG. 19 – WIRING
FORM 150.72-NM1 (908)79JOHNSON CONTROLS55LD13239
JOHNSON CONTROLS8FORM 150.72-NM1 (908)SCHEDULE/ADVANCE DAY KEY ...
JOHNSON CONTROLS80FORM 150.72-NM1 (908)Technical DataMICRO PANEL CONECTIONSLD13240AFIG. 20 – MICRO PANEL CONECTIONS035-21589-102 REV C
FORM 150.72-NM1 (908)81JOHNSON CONTROLS55LD13241A
JOHNSON CONTROLS82FORM 150.72-NM1 (908)Technical DataDIMENSIONS – YLAA0070 TO 0091 (ENGLISH)DIMENSIONS (ENGLISH)FWPDC1R2C2HR1TYPLYLAA ModelL (length)W
FORM 150.72-NM1 (908)83JOHNSON CONTROLS55Water Connection Sizes are shown in the Physical Data Table FWPDC1C2R2R1TYPHBAI1(TYP)I2L5/8” DIA. MOUNTING
JOHNSON CONTROLS84FORM 150.72-NM1 (908)Technical DataDIMENSIONS – YLAA00101 TO 0125 (ENGLISH)Water Connection Sizes are shown in the Physical Data Tab
FORM 150.72-NM1 (908)85JOHNSON CONTROLS55DIMENSIONS – YLAA0135 - 0155 (ENGLISH)Water connection sizes are shown in Physical Data (Table 4).FWPDC1 C2R2
JOHNSON CONTROLS86FORM 150.72-NM1 (908)Technical Data L5/8" DIA. MOUNTING HOLES (TYP)ABI1(TYP)I2I3HR1(TYP)R2C1C2DPFWYLAA Model L (length) W (w
FORM 150.72-NM1 (908)87JOHNSON CONTROLS55TECHNICAL DATA – CLEARANCESNOTES:1. No obstructions allowed above the unit.2. Only one adjacent wall may be
JOHNSON CONTROLS88FORM 150.72-NM1 (908)Technical DataWEIGHT DISTRIBUTION AND ISOLATOR MOUNTING POSITIONSGENERALWeights of specic chiller models vary
FORM 150.72-NM1 (908)89JOHNSON CONTROLS55This Page Intentionally Left Blank
FORM 150.72-NM1 (908)9JOHNSON CONTROLSCHECKING INPUTS AND OUTPUTS ...
JOHNSON CONTROLS90FORM 150.72-NM1 (908)Technical DataISOLATOR LOCATIONSI, I5I2, I6ABTYPTYPI, I5I2, I6I3, I7ABTYPTYPTYPYLAA ModelAVM LOCATIONSI1 I2 I3
FORM 150.72-NM1 (908)91JOHNSON CONTROLS55I, I5I2, I6I3, I7ABTYPTYPTYPYLAA ModelAVM LOCATIONSI1 I2 I3 I4 I5 I6 I7 I8 A BYLAA0070SE19.5 76.6 19.5 76.6 1
JOHNSON CONTROLS92FORM 150.72-NM1 (908)Technical DataI2, I6I3, I7I4, I8BI1, I5ACONTROL PANEL ENDYLAA ModelAVM LOCATIONSI1 I2 I3 I4 I5 I6 I7 I8 A BYLAA
FORM 150.72-NM1 (908)93JOHNSON CONTROLS55CPMountTypeDimension Data (Inches)W D L B C T HCP13 5/8 7-3/4 6-1/2 4-3/4 1/2 5-5/8CP23 5/8 10-1/2 9-1/4 7-3/
JOHNSON CONTROLS94FORM 150.72-NM1 (908)Technical DataONE INCH DEFLECTION SPRING ISOLATORS INSTALLATION INSTRUCTIONSUnits shipped on or after June 15,
FORM 150.72-NM1 (908)95JOHNSON CONTROLS55Y2RSVMC PART NUMBER VMC ISOL. COLOR WEIGHT RANGE (LBS) WEIGHT RANGE (KGS)Y2RSI-2D-460 GREEN Up thru 391 UP TO
JOHNSON CONTROLS96FORM 150.72-NM1 (908)Technical DataSEISMIC ISOLATOR INSTALLATION AND ADJUSTMENTLD13763AUnits shipped on or after June 15, 2008WASHER
FORM 150.72-NM1 (908)97JOHNSON CONTROLS55RD-Style IsolatorsMOUNTTYPEDIMENSION DATA (INCHES)L W HF AL AD BT CD DWRD1-WR 3.13 1.75 1.25 2.38 0.34 0
JOHNSON CONTROLS98FORM 150.72-NM1 (908)Technical DataINSTALLATION OF DURULENE VIBRATION ISOLATORSUnits shipped on or after June 15, 2008LD13762ADDTOP
FORM 150.72-NM1 (908)99JOHNSON CONTROLS55ISOLATOR INFORMATION FOR UNITS SHIPPED BEFORE JUNE 15, 2008EEEEHTHCWWLHCL"D" Tap - 4 Holes unless
Owner’s manuals and user’s guides for Home Theater Systems Sony KDL-40EX705.
We providing 1 pdf manuals Sony KDL-40EX705 for download free by document types: User Manual

Brand: Sony | Category: Home Theater Systems | Size: 17.36 MB |
10
11
18
19
22
23
25
31
33
36
39
46
47
47
48
51
62
70
80
80
88
93
98
98
102
106
107
111
112
114
117
120
126
130
132
136
136
142
143
144
145
149
150
150
151
152
157
162
164
165
168
169
169
170
171
174
177
178
183
185
188
190
191
195
199
203
211
| Models | Document Type |
|---|---|
| KDL-32V5610 |
User Manual
Sony KDL-32V5610 Benutzerhandbuch,
327 pages
|
| KDL-22PX300 |
User Manual
Sony KDL-22PX300 User Manual,
297 pages
|
| BDV-E370 |
User Manual
Sony BDV-E370 Manuale d'uso,
2 pages
|
| KDL-50W805B |
User Manual
Sony KDL-50W805B User Manual,
376 pages
|
| KDL-40R453B |
User Manual
Sony KDL-40R453B User Manual,
2 pages
|
| KF-50SX300 |
User Manual
Sony KF-50SX300 Benutzerhandbuch,
229 pages
|
| BDP-S1100 |
User Manual
Sony BDP-S1100 Benutzerhandbuch,
144 pages
|
| BDV-E190 |
User Manual
Sony BDV-E190 Manuale d'uso,
16 pages
|
| KDL-32EX600 |
User Manual
Sony KDL-32EX600 Benutzerhandbuch,
334 pages
|
| KDL-40V3000 |
User Manual
Sony KDL-40V3000 Benutzerhandbuch,
312 pages
|
| KDL-50W805B |
User Manual
Sony KDL-50W805B Manuale d'uso,
2 pages
|
| KDL-19BX200 |
User Manual
Sony KDL-19BX200 Benutzerhandbuch,
194 pages
|
| KDL-19S5500 |
User Manual
Sony KDL-19S5500 Benutzerhandbuch,
235 pages
|
| VPL-PX30 |
User Manual
Sony VPL-PX30 Benutzerhandbuch,
80 pages
|
| HT-DDWG700 |
User Manual
Sony HT-DDWG700 Manuale d'uso,
2 pages
|
| SS-NA2ES |
User Manual
Sony SS-NA2ES Benutzerhandbuch,
12 pages
|
| KDL-32V4000 |
User Manual
Sony KDL-32V4000 Benutzerhandbuch,
121 pages
|
| DVP-FX780 |
User Manual
Sony DVP-FX780 User Manual,
132 pages
|
| KDL-32EX600 |
User Manual
Sony KDL-32EX600 Manuale d'uso,
86 pages
|
| KDL-37U3000 |
User Manual
Sony KDL-37U3000 Benutzerhandbuch,
137 pages
|
Commenti su questo manuale