CONTENTSGENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2NOMENCLATURE . . . . . . . . . . . . . . .
10 Unitary Products GroupSuperheat Charging MethodNOTE: Use this method only during system maintenance andrepair.1. Operate system until temperatur
035-17421-000 Rev B (700)Unitary Products Group 11option out-door thermostat can be used to turn on only the first stage of electric heat if the tem
12 Unitary Products Groupbelow approximately 31F. If the room thermostat opens dur-ing defrost, the control will resume operation in defrost when t
035-17421-000 Rev B (700)Unitary Products Group 13tioning unit.1. The outdoor fan should be running, with warm air beingdischarged from the top of t
14 Unitary Products GroupTable 3: - Superheat ValueINDOOR WB °F*OUTDOOR DB°F55 60 65 70 75 80 85 90 95 100 105 110 11550 9 752 12 10 654 14 12 10
035-17421-000 Rev B (700)Unitary Products Group 15Table 5: Freon 22 Saturation PropertiesTEMP°FPRESSUREPSIGTEMP°FPRESSUREPSIGTEMP°FPRESSUREPSIGTEMP°
035-17421-000 Rev B (700)Heating and Air ConditioningUnitary Products Group5005 York Drive, Norman, Oklahoma 73069 Subject to change without notice.
2 Unitary Products GroupGENERALThe outdoor units are designed to be connected to a match-ing indoor coil with sweat connect lines. Sweat connect un
035-17421-000 Rev B (700)Unitary Products Group 3UNIT INSTALLATIONLOCATIONBefore starting the installation, select and check the suitability of the
4 Unitary Products Group2. Remove the shipping carton and inspect for possibledamage.3. Compressor tie-down bolts should remain tightened.4. Positi
035-17421-000 Rev B (700)Unitary Products Group 55. Total line lengths are limited to 75 feet due to the storagecapacity of the accumulator. Systems
6 Unitary Products Group2. Braze the liquid line to the liquid valve at the outdoorunit. Be sure to wrap the valve body with a wet rag. Allowthe ni
035-17421-000 Rev B (700)Unitary Products Group 7ORIFICE SELECTIONYORKMATE FLOW CONTROL COILSNOTE: The proper orifice must be installed in the indoo
8 Unitary Products Group FIGURE 7 : TYPICAL 1 PHASE FIELD WIRING (AIR HANDLER / ELECTRICAL HEAT) FIGURE 8 : TYPICAL 3 PHASE FIELD WIRING (AIR HAN
035-17421-000 Rev B (700)Unitary Products Group 9After the thermostat is mounted, route the 24-volt control wir-ing (NEC Class 2) from the thermosta