York 90 Manuale di Servizio

Navigare online o scaricare Manuale di Servizio per Pompe di calore York 90. York 90 Technical data Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa

Sommario

Pagina 2

1-6 035B40022-000REFRIGERANT OIL DATASafety Data OilClassification Non-hazardousIn contact with skin Minimally irritating. No first aid necessary. Exe

Pagina 3

2 PRODUCT DESCRIPTION2.1 IntroductionThe YCWM/YCRM range of twin refrigerant circuitwater chillers are designed to be located inside theplant room of

Pagina 4 - I-ii 035B40022-000

2.2 General SpecificationYCWM/YCRM models are completely assembledwith all interconnecting refrigerant piping andwiring ready for field installation.

Pagina 5 - 1 SUPPLIER INFORMATION

2.8 Power and ControlsAll controls and motor starting equipmentnecessary for full unit operation are factory wiredand tested. The power and control co

Pagina 6 - 1-2 035B40022-000

2.10 Nomenclature2-4 035B40022-000YC W M - B 90YORK CHILLERW - WATER COOLEDR-REMOTEAIRCOOLEDPRODUCT TYPEREFRIGERANTBlank = R22B = R407CMODEL(NOMINAL k

Pagina 7 - 035B40022-000 1-3

3 TRANSPORTATION, HANDLINGAND STORAGEYCWM/YCRM series chillers are supplied fullyassembled.YCWM units are pre-charged with refrigerant andoil in the c

Pagina 8 - 1-4 035B40022-000

3.3 AnchorageYCWM/YCRM series chillers are provided with18 mm diameter holes in the base frame forretaining the unit if required.3.4 StorageIf the uni

Pagina 9

4 INSTALLATION4.1 LocationBefore installing the unit, make surethat the building structure and/ormounting surface can support the unitweight. Overall

Pagina 10 - 1-6 035B40022-000

Before filling the system, ensure that it isfree from foreign matter, sand, stones,rust flakes, solder, slag or other materialswhich could damage the

Pagina 11 - 2 PRODUCT DESCRIPTION

4.4 Water ConnectionsThe water inlet and outlet connectionsmust be connected correctly as shown onthe labels fitted next to the fittings.Connect the e

Pagina 13 - YCWM Models 170 to 280

Refrigerant ConnectionsUnits are supplied with a nitrogen holdingcharge.This should be relieved carefully via thesuction service connections and the l

Pagina 14 - 2-4 035B40022-000

035B40022-000 4-5PEL11L3335102453739L224361125612263840(COMMON)(COMMON)(COMMON)(COOLING)(COOLING)(HEATING)(HEATING)(NO)UNIT TERMINAL BOARD EXTERNAL TE

Pagina 15 - AND STORAGE

4-6 035B40022-000PEL11L33351045537413943L2243611466124738424044(COMMON)(COMMON)(COMMON)(COOLING)(HEATING)(HEATING)(COOLING)(NO)UNIT TERMINAL BOARD EXT

Pagina 16 - 3-2 035B40022-000

5 COMMISSIONINGThe unit must be started by trainedpersonnel from an Authorised YorkService Centre. Failure to satisfy thisrequirement will void the wa

Pagina 17 - 4 INSTALLATION

nAfter around 15 minutes of operation, checkthat no air bubbles are visible through the sightglass on the fluid line.If air bubbles are visible, the u

Pagina 18 - 4-2 035B40022-000

6 OPERATIONYCWM/YCRM series chillers are equipped with anelectronic control and monitoring system asstandard. The system provides control, monitoringa

Pagina 19 - 035B40022-000 4-3

6.1 Control PanelItem FunctionDisplays operating and faultparameters.SET POINT + key (increasestemperature SET POINT).SET POINT - key (reducestemperat

Pagina 20 - 4-4 035B40022-000

6.4 Alarm Display and ResetAlarms are indicated by the associated panelLED’s and by messages on the display. Details ofthe alarm codes are given below

Pagina 21

Page left intentionally blank6-4 035B40022-000

Pagina 22 - 4-6 035B40022-000

7 MAINTENANCENever release refrigerant to theatmosphere when emptying therefrigerating circuit. Suitable retrievalequipment must be used. If reclaimed

Pagina 23 - 5 COMMISSIONING

Table of Contents1 SUPPLIER INFORMATION1.1 Introduction 1.11.2 Warranty 1.11.3 Safety 1.11.4 Emergency Stops/Shutdown 1.21.5 About this Manual 1.21.6

Pagina 24 - 5-2 035B40022-000

7.3 Refrigerant ChargeNever introduce liquid refrigerant in thelow pressure side of circuit. Extreme caremust be taken to ensure that circuit iscorrec

Pagina 25 - 6 OPERATION

7.7 Thermostatic Expansion ValveYCWM/YCRM refrigerating circuits are providedwith a thermostatic expansion valve with anexternal equaliser. Valves are

Pagina 26 - 2 035B40022-000

Page left intentionally blank7-4 035B40022-000

Pagina 27 - 035B40022-000 6-3

8 TROUBLE SHOOTINGThe following table details possible unit faults, their probable cause and suggested remedies. For anyother problems not immediately

Pagina 28 - 6-4 035B40022-000

Fault Probable Cause RemedyOne or both compressors notworking.Power circuit interrupted. Check power circuit for earthleakage and shorts. Check fuses.

Pagina 29 - 7 MAINTENANCE

9 TECHNICAL DATA9.1 Pressure Drop Graphs035B40022-000 9-1Pressure Drop kPaFlow Rate m³/h45678 9 10 15 20 25 30 35 45 514045971015253540452030507510012

Pagina 30 - 7-2 035B40022-000

9-2 035B40022-000Pressure Drop kPaFlow Rate m³/h45678 9 10 15 20 25 30 35 45 5140561082010040906070305080125150175200225791201509075756060YCWM and YCR

Pagina 31 - 035B40022-000 7-3

035B40022-000 9-3Pressure Drop kPaFlow Rate m³/h678 9 10 15 20 25 30 35 45 50 55 60 654010111215141325303550454075100125150175200250225275201501209075

Pagina 32 - 7-4 035B40022-000

9.2 Safety Switch Settings9.3 Operational Limits9-4 035B40022-000YCWM/YCRM60 75 90 120 150 170 200 240 280Low Pressure Switchbar 0,5High Pressure Swit

Pagina 33 - 8 TROUBLE SHOOTING

9.4 Physical Data035B40022-000 9-5YCWM/YCRM60 75 90 120 150Refrigerant Circuits22222Refrigerant chargeR22 kg 2 2,2 3 4 4,5per circuitR407C kg 2,3 2,6

Pagina 34 - 8-2 035B40022-000

7 MAINTENANCE7.1 General Requirements 7.17.2 Daily Maintenance 7.17.3 Refrigerant Charge 7.27.4 Compressors 7.27.5 Filter Drier 7.27.6 Sight Glass 7.2

Pagina 35 - 9 TECHNICAL DATA

9.5 Unit Electrical Data9.6 Compressor Electrical Data9-6 035B40022-000YCWM/YCRMModel6075 90 120 150CurrentNom. Cond.30 35 45 64 76Input (A)Max. Cond.

Pagina 36

9.7 Sound Power Levels9.8 Space Requirements035B40022-000 9-7YCWM/Standard Units Units with Acoustic KitYCRMR22R407C R22 R407CModelSoundSound Sound So

Pagina 37 - 035B40022-000 9-3

9.9 Dimensions9-8 035B40022-000JKKYCRMADNOBCJIIHEFMLLYCWMEV 2EV 1CD 1CD 2HGEFEV 2EV 1GAAAANote:EV = EvaporatorCD = CondenserYCWMEvaporator CondenserMo

Pagina 38 - 9-4 035B40022-000

035B40022-000 9-9AEDFCBIKKJQQRROGHLMNPOutletetSensorSensorPocketInlet SensorensorPocket4"4"4"4"ACCESS0RYCondenser Manifold KitACCE

Pagina 39 - 9.4 Physical Data

9-10 035B40022-000PCABNOIL MKFJR RGHE DTSModelABCDEFGH I JKLMNOPRST170 2200 1600 800 398 1500 618 368 1570 50 60 1237 147 157 500 141 760 3" 1 1/

Pagina 40 - 9-6 035B40022-000

9.10 Process and Instrumentation Diagrams035B40022-000 9-11YCWM, YCRM, YCWM-B and YCRM-B Models 60 to 150

Pagina 41 - 9.8 Space Requirements

9-12 035B40022-000YCWM, YCRM, YCWM-B and YCRM-B Models 170 to 280

Pagina 42 - 9-8 035B40022-000

10 SPARE PARTS10.1 Recommended SparesThe table below lists the recommended spares for one unit for 2 years.10.2 Recommended Compressor OilsThe table b

Pagina 43 - 035B40022-000 9-9

This page left intentionally blank10-2 035B40022-000

Pagina 44 - 9-10 035B40022-000

11 DE-COMMISSIONING,DISMANTLING AND DISPOSALNever release refrigerant to theatmosphere when emptying therefrigerating circuits. Suitable retrievalequi

Pagina 45 - 035B40022-000 9-11

1 SUPPLIER INFORMATION1.1 IntroductionYork YCWM/YCRM Series chillers aremanufactured to the most stringent design andconstruction standards to ensure

Pagina 46 - 9-12 035B40022-000

This page left intentionally blank11-2 035B40022-000

Pagina 48 - 10-2 035B40022-000

Subject to change without noticeALL RIGHTS RESERVEDPart No. 035B40022-000 (04/99)YORKEurope

Pagina 49 - DISMANTLING AND DISPOSAL

The unit contains refrigerant vapourand liquid under pressure within theheat exchangers, compressors andpipework. Release of refrigerant canbe a dange

Pagina 50 - 11-2 035B40022-000

1.6 Safety LabelsThe following labels are fitted to each unit.Refrigerant Identification LabelUnit Identification LabelElectrical Warning LabelCrankca

Pagina 51

1.7 Material Safety Data1-4 035B40022-000Refrigerant Data:Safety Data R22, R407CToxicity Low.In contact with skin Liquid splashes or spray may cause f

Pagina 52 - ALL RIGHTS RESERVED

035B40022-000 1-5Hazardous reactions May react violently with sodium, potassium, barium and other alkali andalkaline earth metals. Incompatible materi

Commenti su questo manuale

Nessun commento